CTV15-1,9 CTV - 2-way zone valve, DN10-20, adjustable kvs

2-way zone valve

Specifications

Specifications for CTV15-1,9
Connection G 3/4"
Actuator connection M28 x 1,5
Stroke 3.5 mm
Nominal diameter DN15
Kvs, adjustable 0.17…1.9 m³/h
Max. diff. pressure 150 kPa
Specifications for CTV - 2-way zone valve, DN10-20, adjustable kvs
Application Heating, Cooling, Chilled beams, Radiator
Pressure rating PN10
Connection types BSP externally threaded according to ISO 228/1
Flow characteristics Linear
Leakage 0.0 % of Kvs (PTFE gasket, carbon-filled 25 %, no leakage)
Media Hot water, Cold water, Glycol-mixed water (max. 30 % glycol)
Closing direction When stem is pushed inward
Media temperature 2…90 °C
Body Chromed Brass CW614N
Seat Brass CW614N
Plug Stainless steel 1.4305
Stem Stainless steel 1.4305
Seat packing NBR
O-rings EPDM
Stuffing box Dezincification resistant brass CW 602N
Bonnet Brass CW614N

Accessories