Regio Midi – Pre-programmed room controllers with communication
Regio Midi are controllers with a built-in temperature sensor and an RS485 communication port. Controllers in different rooms and zones can be connected to a bus line enabling communication with a central SCADA system via RS485 (EXOline, BACnet (only display versions) or Modbus).
Navigate on this page
Articles
(19 st)-
RC-C3
- Occupancy button / Forced ventilation
- -
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- X
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- X
- Display
- -
-
RC-C3H
- Occupancy button / Forced ventilation
- -
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- -
- Hidden setpoint
- X
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- X
- Display
- -
-
RC-C3-BLACK
- Dimensions, external (WxHxD)
- 95*95*31 mm
- Supported protocols
- EXOline, Modbus
- AI
- 1
- UI
- 1
- DI
- 1
- DI/CI
- 1
- UO
- 3
- DO
- 0
- Analogue inputs type (AI)
- PT1000, 0...50°C, 0...10 V
- Universal inputs type (UI)
- PT1000 / DI
- Condensation inputs type (CI)
- Digital input for condensation detector KG-A/1
- Universal outputs type (UO)
- DO 24 V AC/1A, AO 0...10 V/5mA
- Accuracy, temperature 1
- ±0.5 °K @ 15...30 °C
- Colour, cover
- RAL9005
- Occupancy button
- False
- 3-step fan control
- False
- EC Fan Control
- True
- Setpoint knob
- True
- Hidden setpoint
- False
- Built-in CO2 sensor
- False
- Display
- False
-
RC-C3H-BLACK
- Dimensions, external (WxHxD)
- 95*95*38 mm
- Supported protocols
- EXOline, Modbus
- AI
- 1
- UI
- 1
- DI
- 1
- DI/CI
- 1
- UO
- 3
- DO
- 0
- Analogue inputs type (AI)
- PT1000, 0...50°C, 0...10 V
- Universal inputs type (UI)
- PT1000 / DI
- Condensation inputs type (CI)
- Digital input for condensation detector KG-A/1
- Universal outputs type (UO)
- DO 24 V AC/1A, AO 0...10 V/5mA
- Accuracy, temperature 1
- ±0.5 °K @ 15...30 °C
- Occupancy button
- False
- 3-step fan control
- False
- EC Fan Control
- True
- Setpoint knob
- False
- Hidden setpoint
- True
- Built-in CO2 sensor
- False
- Display
- False
-
RC-C3DOC
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- -
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- X
- Display
- X
-
RC-C3O
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- X
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- X
- Display
- -
-
RC-CF
- Occupancy button / Forced ventilation
- -
- 3-step fan control
- X
- EC fan control
- -
- Setpoint knob
- X
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- -
- Display
- -
-
RC-C3DFOC
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- -
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- X
- Display
- X
-
RC-CT
- Occupancy button / Forced ventilation
- -
- 3-step fan control
- -
- EC fan control
- -
- Setpoint knob
- X
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 3-point
- 3 universal outputs
- -
- Display
- -
-
RC-CTO
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- -
- EC fan control
- -
- Setpoint knob
- X
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 3-point
- 3 universal outputs
- -
- Display
- -
-
RC-C3DOC-BLACK
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- -
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- X
- Display
- X
-
RC-CDFO
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- X
- EC fan control
- -
- Setpoint knob
- -
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- -
- Display
- X
-
RC-CFO
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- X
- EC fan control
- -
- Setpoint knob
- X
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 0...10 V DC or on/off
- 3 universal outputs
- -
- Display
- -
-
RC-CTH
- Occupancy button / Forced ventilation
- -
- 3-step fan control
- -
- EC fan control
- -
- Setpoint knob
- -
- Hidden setpoint
- X
- Built-in CO 2 sensor
- -
- Output
- 3-point
- 3 universal outputs
- -
- Display
- -
-
RC-CDTO
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- -
- EC fan control
- -
- Setpoint knob
- -
- Hidden setpoint
- -
- Built-in CO 2 sensor
- -
- Output
- 3-point
- 3 universal outputs
- -
- Display
- X
-
RCC-C3DOCS
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- -
- Hidden setpoint
- -
- Built-in CO 2 sensor
- X
- Output
- 0…10 V DC or on/off
- 3 universal outputs
- X
- Display
- X
-
RCC-C3HCS
- Occupancy button / Forced ventilation
- -
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- -
- Hidden setpoint
- X
- Built-in CO 2 sensor
- X
- Output
- 0…10 V DC or on/off
- 3 universal outputs
- X
- Display
- -
-
-
RCC-C3DOCS-BLACK
- Occupancy button / Forced ventilation
- X
- 3-step fan control
- -
- EC fan control
- X
- Setpoint knob
- -
- Hidden setpoint
- -
- Built-in CO 2 sensor
- X
- Output
- 0…10 V DC or on/off
- 3 universal outputs
- X
- Display
- X
Specifications
Supply voltage | 18...30 V AC, 50...60 Hz |
---|---|
Power consumption | 2.5 VA |
Ambient temperature | 0...50°C |
Storage temperature | -20…+70°C |
Ambient humidity | Max. 90 % RH |
Communication | RS485 (EXOline or Modbus with automatic detection/change-over, or BACnet). Note: BACnet communication is only an option for RCC models and models with display. |
Modbus | 8 bits, 1 or 2 stop bits. Odd, even (FS) or no parity. |
Communication speed | 9600, 19200, 38400 bps (EXOline, Modbus and BACnet) or 76800 bps (BACnet only) |
Built-in temperature sensor | 0...50°C NTC linearised 15 kΩ |
Accuracy | ±0.5°C at 15...30°C |
Mounting | Room |
Protection class | IP20 |
Analogue inputs (AI) | PT1000, 0...50°C, 0...10 V |
Condensation input (CI) | Digital input for condensation detector |
Digital inputs (DI) | Closing potential-free contact |
Universal inputs (UI) | Analogue input (AI), PT1000 sensor, 0...100°C or digital input (DI) |
Digital outputs (DO) | 24 V AC, max. 0.5 A |
Universal outputs (UO) | Digital output (DO) 24 V AC, max. 2.0 A or analogue output (AO), 0...10 V DC, max. 5 mA |
+C power output for DI only | 24 V DC, max. 10 mA, short circuit-protected |

RC-CD* and RC-C3D* are BTL listed
Software & documentation
Accessories

RB3
Relay unit for RC-...F... controllers

X1178
Power interface for RC-...F... controllers

KG-A/1
Condensation detector for Regio controllers, 1 m cable length

RC-CONN:10
A set of 10 connector plates for RC units

RCC-CONN:10
A set of 10 connector plates for RCC units

RC-TEST
Service adapter for all Regio room units