Articles

(2 st)
  • RDAS7S-24C - Regin
    RDAS7S-24C
    Supply voltage
    24 V AC/DC (20…28 V AC 50/60 Hz / 24…48 V DC)
    Power consumption
    5 VA (3.5 W - Running / 2 W - Holding)
    Torque
    7 Nm
    Running time, actuator
    90 s
    Running time, spring
    15 s
    Auxiliary switch
    No
    Angle limitation
    95 °
    Damper shaft, round
    6.4…20.5mm mm
    Damper shaft, square
    6.4…13mm mm
    Damper shaft, min shaft length
    20 mm
    Max damper size (area)
    1.5 m²
    Termination RS485
    120 Ω electronically switchable
  • RDAS18S-24C - Regin
    RDAS18S-24C
    Supply voltage
    24 V AC/DC (20…28 V AC 50/60 Hz / 24…48 V DC)
    Power consumption
    7 VA (5W - Running / 3W - Holding)
    Torque
    18 Nm
    Running time, actuator
    90 s
    Running time, spring
    15 s
    Auxiliary switch
    No
    Angle limitation
    95 °
    Damper shaft, round
    8…25.6mm mm
    Damper shaft, square
    6…18mm mm
    Damper shaft, min shaft length
    20 mm
    Max damper size (area)
    3 m²
    Termination RS485
    120 Ω electronically switchable

Specifications

Specifications for 7 Nm, 18 Nm
Appliance class Class III
Protection class IP54
Ambient humidity (non-condensing) 0…95 % RH
Ambient temp -32…55 °C
Storage temp -32…70 °C
Cable length 0.9 m
Cable nominal cross section 0.75 mm²
Cable length extension, maximum 300 m
Working angle, rotation 90 °