Pressure transmitter for liquids and gases

Pressure transmitter for measurement of liquids and gases.

Articles

(14 st)
  • TTKN1 - Regin
    TTKN1
    Working range
    0...100 kPa
    Output signal
    0...10 V DC
    Supply voltage
    12...33 V DC / 24 V AC ±15 %
    Power consumption
    < 7 mA
    Load
    > 10000 Ω
  • TTKN1-420 - Regin
    TTKN1-420
    Working range
    0...100 kPa
    Output signal
    4...20 mA
    Supply voltage
    7…33 V DC
    Power consumption
    < 23 mA
    Load
    ((Supply voltage - 7 V) / 0.02 A) Ω
  • TTKN2.5 - Regin
    TTKN2.5
    Working range
    0...250 kPa
    Output signal
    0...10 V DC
    Supply voltage
    12...33 V DC / 24 V AC ±15 %
    Power consumption
    < 7 mA
    Load
    > 10000 Ω
  • TTKN2.5-420 - Regin
    TTKN2.5-420
    Working range
    0...250 kPa
    Output signal
    4...20 mA
    Supply voltage
    7…33 V DC
    Power consumption
    < 23 mA
    Load
    ((Supply voltage - 7 V) / 0.02 A) Ω
  • TTKN6 - Regin
    TTKN6
    Working range
    0...600 kPa
    Output signal
    0...10 V DC
    Supply voltage
    12...33 V DC / 24 V AC ±15 %
    Power consumption
    < 7 mA
    Load
    > 10000 Ω
  • TTKN6-420 - Regin
    TTKN6-420
    Working range
    0...600 kPa
    Output signal
    4...20 mA
    Supply voltage
    7…33 V DC
    Power consumption
    < 23 mA
    Load
    ((Supply voltage - 7 V) / 0.02 A) Ω
  • TTKN10 - Regin
    TTKN10
    Working range
    0...1000 kPa
    Output signal
    0...10 V DC
    Supply voltage
    12...33 V DC / 24 V AC ±15 %
    Power consumption
    < 7 mA
    Load
    > 10000 Ω
  • TTKN10-420 - Regin
    TTKN10-420
    Working range
    0...1000 kPa
    Output signal
    4...20 mA
    Supply voltage
    7…33 V DC
    Power consumption
    < 23 mA
    Load
    ((Supply voltage - 7 V) / 0.02 A) Ω
  • TTKN16 - Regin
    TTKN16
    Working range
    0...1600 kPa
    Output signal
    0...10 V DC
    Supply voltage
    12...33 V DC / 24 V AC ±15 %
    Power consumption
    < 7 mA
    Load
    > 10000 Ω
  • TTKN16-420 - Regin
    TTKN16-420
    Working range
    0...1600 kPa
    Output signal
    4...20 mA
    Supply voltage
    7…33 V DC
    Power consumption
    < 23 mA
    Load
    ((Supply voltage - 7 V) / 0.02 A) Ω
  • TTKN25 - Regin
    TTKN25
    Working range
    0...2500 kPa
    Output signal
    0...10 V DC
    Supply voltage
    12...33 V DC / 24 V AC ±15 %
    Power consumption
    < 7 mA
    Load
    > 10000 Ω
  • TTKN25-420 - Regin
    TTKN25-420
    Working range
    0...2500 kPa
    Output signal
    4...20 mA
    Supply voltage
    7…33 V DC
    Power consumption
    < 23 mA
    Load
    ((Supply voltage - 7 V) / 0.02 A) Ω
  • TTKN40 - Regin
    TTKN40
    Working range
    0...4000 kPa
    Output signal
    0...10 V DC
    Supply voltage
    12...33 V DC / 24 V AC ±15 %
    Power consumption
    < 7 mA
    Load
    > 10000 Ω
  • TTKN40-420 - Regin
    TTKN40-420
    Working range
    0...4000 kPa
    Output signal
    4...20 mA
    Supply voltage
    7…33 V DC
    Power consumption
    < 23 mA
    Load
    ((Supply voltage - 7 V) / 0.02 A) Ω
Specifications for Pressure transmitter for liquids and gases
Output signal 0...10 V DC (three-wire) or 4...20 mA (two-wire)
Pressure connection G 1/4"
Dynamic response time < 2 ms, 1 ms typically
Tolerable overload ≤ 4 bar 3.0 x full scale, > 4 bar 2.5 x full scale
Media temperature -15…+125°C
Ambient temperature -30…+85°C
Storage temperature -50…+100°C
Accuracy, characteristic line ±0.3 % full scale *
Accuracy, resolution 0.1 % full scale *
Accuracy, thermal characteristic Max. ±0.2 % full scale / 10 K *
Accuracy, long-term stability according to IEC EN 60770-1 Max. ±0.25 % full scale *
Sealing FPM
Weight 90 g
Cable length 1.5m
Protection class IP67

Product sheet

ADAPTER

Adapter 1/4" to 1/2". For mounting immersion sensors in 1/2".

105074

Mounting spacer which lowers the temperature at higher media temperatures than the sensor can handle.