Regin
CTV - 2-way zone valve, DN10-20, adjustable kvs
The valve range is intended to be used together with the RTA(O)M100 thermal actuators for temperature control in heating and cooling systems, such as radiators, convectors, chilled ceilings etc.
Articles
(3 st)-
CTV102-way zone valve- Stroke
- 3.5 mm
- Nominal diameter
- DN10
- Kvs, adjustable
- 0.12…1.14 m³/h
- Max. diff. pressure
- 150 kPa
- Connection
- G 1/2"
- Media temperature
- 2…90 °C
-
CTV15-1,92-way zone valve- Stroke
- 3.5 mm
- Nominal diameter
- DN15
- Kvs, adjustable
- 0.17…1.9 m³/h
- Max. diff. pressure
- 150 kPa
- Connection
- G 3/4"
- Media temperature
- 2…90 °C
-
CTV202-way zone valve- Stroke
- 3.5 mm
- Nominal diameter
- DN20
- Kvs, adjustable
- 0.15…1.55 m³/h
- Max. diff. pressure
- 150 kPa
- Connection
- G1"
- Media temperature
- 2…90 °C
Specifications
| Application | Heating, Cooling, Chilled beams, Radiator |
|---|---|
| Pressure rating | PN10 |
| Connection types | BSP externally threaded according to ISO 228/1 |
| Flow characteristics | Linear |
| Leakage | 0.0 % of Kvs (PTFE gasket, carbon-filled 25 %, no leakage) |
| Media | Hot water, Cold water, Glycol-mixed water (max. 30 % glycol) |
| Closing direction | When stem is pushed inward |
| Actuator connection | M28 x 1,5 |
| Media temperature | 2…90 °C |
| Body | Chromed Brass CW614N |
| Seat | Brass CW614N |
| Plug | Stainless steel 1.4305 |
| Stem | Stainless steel 1.4305 |
| Seat packing | NBR |
| O-rings | EPDM |
| Stuffing box | Dezincification resistant brass CW 602N |
| Bonnet | Brass CW614N |
Software & documentation
Product sheet
Other documentation
Accessories


- Force
- 200 N
- Supply voltage
- 24 V AC/DC
- Control signal
- 0(2)…10 V DC or 0(4)…20 mA

- Force
- 200 N
- Supply voltage
- 230 V AC
- Control signal
- 3-point/2-point

- Force
- 200 N
- Supply voltage
- 24 V AC/DC
- Control signal
- 3-point/2-point

- Force
- 100 N
- Supply voltage
- 24 V AC
- Control signal
- 0...10 V DC, NC

- Force
- 100 N
- Supply voltage
- 24 V AC
- Control signal
- 0...10 V DC, NO