Corrigo Ardo - configurable controllers for ventilation and heating.
This product is discontinued
This product is discontinued
Corrigo comes preloaded with applications for control of ventilation and heating. The Corrigo controllers are BTL listed, click here to go to the BACnet International website where you'll find PICS documents and more information.
Corrigo ventilationCorrigo running a ventilation application is intended for control of air handling units with temperature control, 1- or 2-speed operation or, alternatively, pressure or air flow control of supply air fan and extract air fan, humidity control as well as other common functions in ventilation.
Corrigo heatingCorrigo running a heating application is intended for control of heating substations in buildings. The controller supports control of up to 3 heating circuits and 2 DHW circuits. Corrigo heating also has built-in boiler control for a total of 4 boilers. It can also controll a cooling circuit with dew-point control.
Articles
(0 st)Specifications
Supply voltage | 24 V AC ± 15 %, 50...60 Hz or 21...36 V DC |
---|---|
Power consumption | 8 VA, 4 W (DC), model E...W-3: 12 VA, 6 W (DC) |
Ambient temperature | 0...50°C |
Storage temperature | -20…+70°C |
Ambient humidity | Max. 90 % RH |
Protection class | IP20 |
Connection | Disconnectable terminal strips, 4 mm 2 |
Memory backup | Built-in long life battery gives long backup time of all settings incl. real time |
Display | Backlit LCD (blue), 4 rows of 20 characters |
Mounting | DIN-rail or cabinet |
Number of modules | 8.5 |
Dimensions (WxHxD) | 149 x 121 x 60mm |
Ethernet | Webserver, EXOline, Modbus, BACnet/IP, CLOUDigo |
RS485 | EXOline, Modbus, BACnet MS/TP |
M-Bus ports | M-Bus communication |
Analogue inputs (AI) | For PT1000 sensors (accuracy ± 0.4°C) or 0...10 V DC (accuracy ± 0.15 % of full output signal). 12 bit resolution in the A/D conversion. |
Digital inputs (DI) | For potential-free contacts |
Analogue outputs (AO) | 0...10 V DC, 1 mA, short-circuit proof |
Digital outputs (DO) | Mosfet outputs, 24 V AC or DC, 2 A continuous. Max. 8 A in total. |
Battery type | CR2032 replacable Lithium cell |
Battery life time | 5 years |
Protection class | IP20 |
Ambient humidity (non-condensing) | 0…90 % RH |
Storage temperature | -20…70 °C |
Mounting | Cabinet, DIN-rail |
Analogue inputs type (AI) | PT1000/Ni1000/Ni1000LG/0-10 V |
Terminal type | Screw Terminal |
Detachable terminal | Yes |
Terminal wire size | 3 mm² |
Material, housing | Polycarbonate (PC) |
Material, base | Polycarbonate (PC) |
Software & documentation
- Corrigo ventilation 3.6 (EN)
- Corrigo heating 3.4 (EN)
- Corrigo ventilation 3.X user guide (EN)
- Corrigo heating 3.3 user guide (EN)
- Corrigo ventilation 3.X user guide (TR)
- Corrigo ventilation 3.X user guide (DA)
- Corrigo ventilation 3.X user guide (LV)
- Corrigo ventilation 3.X user guide (SK)
- Corrigo ventilation 3.X user guide (ES)
- Corrigo ventilation 3.X user guide (SI)
- Corrigo ventilation 3.X user guide (HU)
- Corrigo ventilation 3.X user guide (RU)
- Corrigo ventilation 3.X user guide (RO)
- Corrigo ventilation 3.X user guide (CZ)
- Corrigo ventilation 3.X user guide (PT)
- Corrigo ventilation 3.X user guide (PL)
- Corrigo ventilation 3.X user guide (NO)
- Corrigo ventilation 3.X user guide (LT)
- Corrigo ventilation 3.X user guide (NL)
- Corrigo ventilation 3.X user guide (FI)
- Corrigo ventilation 3.X user guide (ET)
- Corrigo ventilation variables for EXOline Modbus and BACnet 3.6 (EN)
- Corrigo/Exigo heating variables for EXOline Modbus and BACnet 3.4 (EN)
- CAB-STD2-3 Corrigo ventilation 3.6 editable (EN)
- CAB-STD1-3 Corrigo ventilation 3.4 editable (EN)
- CAB-STD1-3 Corrigo heating 3.4 editable (EN)
- Information on updates in Corrigo ventilation (from version 3.3-1-25) (EN)
- Information on updates in Corrigo heating (from version 3.3-1-06) (EN)
- Env. decl. (EN)
- Corrigo ventilation 3.6 BACnet EDE
- Corrigo ventilation 3.6 BACnet Object Types
Accessories


The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

- RS485 ports
- 1
- Ethernet ports
- 1
- Number of I/O
- 28

- RS485 ports
- 1
- Ethernet ports
- 1
- Number of I/O
- 15

- RS485 ports
- 1
- Ethernet ports
- 1
- Number of I/O
- 19