Regin

PDTN12S12-C Presigo (PDTN…) - Differential pressure transmitters

Presigo PDTN,Diff. pressure transmitter, 0-1250Pa & 0-2500Pa, communication

Specifications

Specifications for PDTN12S12-C
Sensor Interface BACnet MS/TP, Modbus RTU, EXOline
Display No
Max Overvoltage on any terminal Max. ±18 V (referenced to GND) V
Measuring range pressure 0…1250 Pa/0…1250 Pa
Pressure, range sensor 1 0…1250 Pa
Pressure, range sensor 2 0…1250 Pa
Accuracy, pressure sensor 1 ≤ 1,5 % full scale %
Accuracy, pressure sensor 2 ≤ 1,5 % full scale %
Max. allowed diff. Pressure sensor 1 35 kPa
Max. allowed diff. Pressure sensor 2 35 kPa
Specifications for Presigo (PDTN…) - Differential pressure transmitters
Power Supply 24VAC/DC (21...27 V AC 50Hz / 21...27 V DC), 2.0 VA
Protection class IP54
Ambient humidity (non-condensing) 0…95 % RH
Ambient temperature -25…50 °C
Mounting Wall
Dimensions, external (WxHxD) 120x40x112 mm
Media Air, non-combustible and non-aggressive gases
Damping (electronic) 0…600s
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
Material, housing Polycarbonate (PC)
Material, base Polycarbonate (PC)

Configuration tools

You´re on Denmark site Change sales company?
Austria Benelux France Germany International Italy (Redirect to: industrietechnik.it) Sweden Switzerland