Regin
SSCU80-40-HR-MPI Flanged ultrasonic energy meters
Dit artikel is uit productie genomen
Flanged ultrasonic energy meters, intended for heating or cooling.We offer many different options, see the product sheet for more information.
Specificaties
| Power Supply | Exchangeable 3 V lithium battery, estimated lifetime 10 years. 24 V or 230 V power pack available as accessory. |
|---|---|
| Nominal diameter | DN80 |
| Flow, Qp | 40 m³/h |
| Type of measurement | Heating |
| Communication interface | M-Bus with 3 pulse inputs |
| Length of flow meter | 300 mm |
| Media | Water only |
| Protection class | IP54 |
|---|---|
| Ambient humidity (non-condensing) | 5…95 % RH |
| Storage temperature | 1…60 °C |
| Temperature range cooling | 0...50 °C |
| Temperature range heating | 0...150 °C |
| Temperature resolution | 0.01 °C |
| Measurement cycle, temperature | 2...60 s |
| Measurement cycle, flow | 2 s |
| Display | LCD, 8 digits + special characters |
| Display units | MWh, kW, GJ, m 3 , m 3 /h (kWh, GJ, l , l/h, MW, MMBTU, Gcal), 3 decimal places. The unit for energy consumption can only be set while the energy consumption is ≤ 10 kWh. |
| Mechanical class | Class M2 (MID: 31.03.2004 annex I) |
| EMC | Class E2 (MID: 31.03.2004 annex I) |
| Cable length temperature sensor | 3 m |
| Diameter temperature sensor | 6 mm |
| Temperature sensor installation | Indirect in a temperature sensor pocket per EN1434 |
| Temperature sensor requirements, heat meter | EU (MID) identification on the temperature sensors |
| Temperature sensor requirements, cooling meter | National German approval as a temperature sensor for cooling meters. Requirements in other countries may be different |
| Flow meter mounting position | Horizontal or vertical, the transducers (black housing) to the side of or under the measuring tube for cooling applications |
| Flow meter, point of installation | Return flow (if forward flow installation is needed, the installation position can be changed with the main button) |
| Flow meter temperature range | Heating 10…130 °C |
| Measuring principle | Ultrasonic; time-of-flight |
| Accuracy according to MID | Class 2 |
Software en documentatie
Andere documentatie
Accessoires



Regin
TH-120-1/2
Temperature sensor pocket for installation of universal temperature sensor with 6 mm sheath diameter
- Compatible with
- 15...100 m³/h
- Connection A
- G1/2"
- Installation length
- 120 mm

Regin
TH-85-1/2
Temperature sensor pocket for installation of universal temperature sensor with 6 mm sheath diameter
- Compatible with
- q p 3.5…10 m 3 /h
- Connection A
- G½
- Installation length
- 85 mm