Articles
(2 st)-
SDD-OE65Optical detector with service alarm (max 20 sensors, to be connected to CABV control unit) including 600 mm Venturi tube.- Power Supply
- 9...33 V DC (via ABV control unit)
- Service alarm
- Red LED on detector. Yellow LED on control unit.
- Current consumption, normal
- 10 mA
- Current consumption during alarm
- 50 mA
- Current consumption during service alarm
- 20 mA
- End resistor
- An end resistor (2,2 kΩ) should be connected to the last detector to end the loop.
-
SDD-OE65-RACOptical detector with AC power supply and relay output only, with service alarm, including 600 mm Venturi tube.- Power Supply
- 24 V AC ±15 % for RAC(M) models.
- Service alarm
- Red LED on detector. Yellow LED on control unit.
- Current consumption, normal
- 10 mA
- Current consumption during alarm
- 50 mA
- Current consumption during service alarm
- 20 mA
- Relay
- Max 24 V AC / 2A or 24 V DC / 1A (Resistive load)
- End resistor
- An end resistor (2,2 kΩ) should be connected to the last detector to end the loop.
Specifications
| Protection class | IP54 |
|---|---|
| Ambient humidity (non-condensing) | 5…95 % RH |
| Mounting | Duct |
| Wind speed | Up to 20 m/s |
| Smoke alarm | Red LED |
Software & documentation
Instructions