E281D-3 Corrigo Ardo - configurable controllers for heating only
This article is discontinued
Corrigo preloaded with application for control of heating.
Specifications
Inputs | 16 |
---|---|
Outputs | 12 |
Dual ports |
Supply voltage | 24 V AC ±15 %, 50...60 Hz or 20...36 V DC |
---|---|
Power consumption | 5 VA, 3 W (DC) WEB models: 9 VA, 5 W (DC) |
Ambient temperature | 0...50°C |
Storage temperature | -40...+50°C |
Ambient humidity | Max. 90 % RH |
Protection class | IP20 |
Memory backup | Built-in long-life battery with long time back-up of all settings |
Display | Backlit, LCD, 4 rows of 20 characters |
Dimensions (WxHxD) | 148 x 123 x 58mm |
Mounting | DIN-rail |
Communication | RS485, EXOline (free protocol) and Modbus as standard. LON and TCP/IP as options. |
Analogue inputs (AI) | For a PT1000 sensor or 0...10 V DC |
Digital inputs (DI) | For potential-free contacts |
Analogue outputs (AO) | 0...10 V DC, 1 mA, short-circuit proof |
Digital outputs (DO) | Mosfet 2 A each, max. 8 A total, 24 V AC or DC |
Software & documentation
- Corrigo/Exigo heating variables for EXOline Modbus and BACnet 3.4 (EN)
- CAB-STD1-3 Corrigo heating 3.4 editable (EN)
- Information on updates in Corrigo heating (from version 3.3-1-06) (EN)
- Env. decl. (EN)
- CAB-STD1-3 Corrigo ventilation 3.4 editable (EN)
- Corrigo ventilation 3.6 BACnet EDE
- Corrigo ventilation 3.6 BACnet Object Types
- Information on updates in Corrigo ventilation (from version 3.3-1-25) (EN)
- E281D-3, CE decl. (EN)
Accessories


The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

The ED-RU units can be connected to several different products and could, for example, be used to control an air…

- RS485 ports
- 1
- Ethernet ports
- 1
- Number of I/O
- 28

- RS485 ports
- 1
- Ethernet ports
- 1
- Number of I/O
- 15

- RS485 ports
- 1
- Ethernet ports
- 1
- Number of I/O
- 19