Duct/wall humidistat
                                        
                                        
                                                    
                                                        
- Dimensions, external (WxHxD)
- 104x98x74 mm
                                                        
- Medium
- Air/Gas
                                                        
- Mounting
- Wall/(Room)
                                                        
- Reset function
- Automatic
                                                        
- Conformity
- CE
                                                        
- Contact type
- 1 step, change-over contact, NO/NC, Not suitable for DC circuits
                                                        
- Switching load
- 10 A, 250 VAC resistive at 25 °C ambient 8 A, 250 VAC resistive at 60 °C ambient
                                                        
- Electrical connection
- Screw terminal
                                                        
- Cable inlet
- PG11, cable Ø6 - 10mm
                                                        
- Sensitive element
- Organic fiber (hygroscopic hair type)
                                                        
- Measuring range, humidity
- 10…100 %RH
                                                        
- Hysterisis, humidity
- 3% RH @45% RH