Controller intended for control of valve actuators in water-heated systems. It has a built-in room sensor and can be used for control of supply air temperature or room temperature, with or without cascade control. The controller has built-in active frost protection with two alarm relays and automatic heat maintaining function during shutdown.
Navigate on this page
Specifications
Supply voltage | 24 V AC ±10 %, 50/60 Hz |
---|---|
Power consumption | Max. 5 VA |
Control signal (output) | 3-point floating control, 24 V AC output (heating) |
Sensor inputs | Three 0...30°C (the sensor determines the range (NTC sensor)) |
Setpoint | 0...30°C |
Minimum limit | 0...30°C (not active for single sensor control) |
Cascade factor (CF) | 1…15 |
Frost alarm setpoint | 5 °C |
Shutdown mode setpoint | 25°C |
Fan relay | Breaking contact for fan contactor interlock if a frost protection alarm occurs. 230 V AC, 2 A. |
Alarm relay | Change-over contact for alarm indication if a frost protection alarm occurs. 24 V AC, 2 A. |
Mounting | Wall |
Dimensions | 93 x 153 x 40mm |