CTV15-1,9 CTV - 2-way zone valve, DN10-20, adjustable kvs

2-way zone valve
Specifications for CTV15-1,9
Nominal diameter DN15
Connection, external thread G3/4"
Kvs (adjustable) 0.17…1.9 m3/h
Actuator RTA(O)M100, RVAZ2
Specifications for CTV - 2-way zone valve, DN10-20, adjustable kvs
Application Heating systems, cooling systems, radiators
Pressure rating PN10
Connection BSP externally threaded according to ISO 228/1
Connection, actuator M28 x 1.5
Flow characteristics Linear
Max. leakage 0.0 % of the kvs value
Max. diff. pressure 150kPa
Media Hot water, cold water, glycol-mixed water
Media temperature 2…90°C
Stroke 3.5mm
Body Chromed brass CW614N
Seat Brass CW614N
Stem Stainless steel 1.4305
O-rings EPDM
Bonnet Brass CW614N
Seat packing NBR
1885136

Nut and olive

1886274

Nut and olive

1884709

Nut and olive

1886282

Nut and olive