OP10 Optigo - Controllers for simple applications

Controller for temperature.
Specifications for OP10
Supply voltage 24 V AC ±15 %
Number of I/Os 10
Specifications for Optigo - Controllers for simple applications
Supply voltage 24 V AC ±15 % / ...10-230 model: 230 V AC
Power consumption 4 VA
Ambient temperature 0…50°C
Storage temperature -40…+50°C
Ambient humidity Max. 90 % RH
Mounting DIN-rail
Number of modules 7
Protection class IP20
Display Backlit LCD, numeric/graphic, language-independent symbols
Dimensions (WxHxD) 123 x 123 x 60mm
Clock Week-based 24-hour clock
Analogue inputs (AI) PT1000
Digital inputs (DI) Closing potential-free contact
Universal inputs (UI) 0...10 V DC or digital
Setpoint input (SPI) For an external PT1000 setpoint device, e.g. TG-R4/PT1000 or TBI-PT1000
Analogue outputs (AO) 0...10 V DC, short-circuit protected
Digital outputs (DO) OP10 and OP10-230 only. Triac 24 V AC, 0.5 A (3-point control or alarm output) and one change-over relay 230 V AC, 5 A (fan start).
FMCO

Front mounting kit, room for one Optigo unit

PLTCE

Set of angled plug-in terminal blocks