Add:io, additional I/O units

Additional I/O unit for the freely programmable controllers EXOcompact and EXOclever with 16 supplementary I/Os per Add:io. Possibility to expand an EXOclever controller with unlimited I/Os and an EXOcompact with up to 50 I/Os. The Add:io units fit smoothly together, requiring minimal space.

Articles

(2 st)
  • IO-EC16UID-X - Regin
    IO-EC16UID-X
    Universal input d (UId)
    16
    Universal output b (UOb)
    -
  • IO-EC16UOB-X - Regin
    IO-EC16UOB-X
    Universal input d (UId)
    -
    Universal output b (UOb)
    16
Specifications for Add:io, additional I/O units
Supply voltage 24 V AC/DC (18…26 V AC / 22…30 V DC)
Power consumption, nominal IO-…16UOb: 7.8 VA / 3.5 W
IO-…16UIc and …16UId: 4.5 VA / 1.8 W
Protection class IP20
Ambient humidity Max. 95 % RH
Ambient temperature 0…55°C
Ambient temperature, electronics 0…55°C
Storage temperature -20…+70°C
Mounting DIN-rail
Number of modules 8
Inputs/outputs (I/Os) 16 per Add:io
Display No
Indication type LED for communication info
Dimensions, external (WxHxD)

140 x 136 x 46

mm
Weight (incl. packaging) 0.30 kg
Port type RS485
Default protocol

EFX

Supported protocols

EFX slave

Port isolation

Yes

Communication speed

115200 bps

Cable connection Push-in connectors
Universal input c (UIc) AI: 0…10 V, 800…1600 Ω (Pt1000, Ni1000 LG, Ni1000 DIN), 0…4000 Ω (Pt1000 ext, Ni1000 LG ext, Ni1000 DIN ext)
DI: Sourcing input type, GND is ref
Universal input d (UId) AI: 0…10 V, 0(4)…20 mA, 800…1600 Ω (Pt1000, Ni1000 LG, Ni1000 DIN), 0…4000 Ω (Pt1000 ext, Ni1000 LG ext, Ni1000 DIN ext)
DI: Sourcing input type, GND is ref
Universal output b (UOb) AO: 0…10 V DC, short-circuit protected
DO: 24 V AC/DC sinking MOSFET, DC short-circuit protected
Material, housing Polycarbonate, PC