Regin
DTL10/10-D Differential pressure transmitter for air
This article is discontinued
Transmitter for differential pressure measurement of air and non-corrosive gases in air handling units, etc. A common application area is pressure control in ventilation systems.
Specifications
| Display | Yes |
|---|---|
| Output signal | 0…10 V DC (settable to 4…20 mA via DIP-switch) |
| Supply voltage | 21…27 V AC or 18…33 V DC. (4…20 mA only 18…33 V DC) |
|---|---|
| Measuring range | -30…+30 Pa / -50…+50 Pa / -100…+100 Pa |
| Ambient temperature | 0…70°C |
| Protection class | IP54 |
| Accuracy, linearity | < ±1.0 % full scale |
| Accuracy, hysteresis | < ±1.0 % full scale |
| Accessories, included | Two pressure outlets (straight) and 2 m plastic tube. Art. no.: ANS-20 |
Software & documentation
Product sheet
Instructions
Other documentation
Accessories