Specifications for CO2 transmitter, room mounting
Supply voltage 24 V AC ±10 % / 15...35 V DC
Working range, CO 2 0…2000ppm
Working range, temperature 0…50°C
Working range, humidity 10...90% RH
Accuracy, CO 2 < ± (50 ppm + 2 % of the measured value) (25 °C)
Accuracy, temperature ±3 % °C
Accuracy, humidity ±3 % RH (20°C)
Mounting Room
Protection class IP30
CO 2 0...10 V DC referring to 0...2000 ppm
Temperature 0...10 V DC referring to 0...50°C
Humidity 0...10 V DC referring to 0...100 % RH