I/O module with 7 or 10 inputs/outputs

I/O module for expansion of Regin’s freely programmable EXOclever, EXOflex, EXOcompact and EXOdos controllers.

Articles

(2 st)
  • IO-RU-7 - Regin
    IO-RU-7
    Total number of I/O:s
    7
    DO
    -
    UO
    3
    AI
    1
    DI
    2
    UI
    1
  • IO-RU-10 - Regin
    IO-RU-10
    Total number of I/O:s
    10
    DO
    4
    UO
    2
    AI
    1
    DI
    2
    UI
    1
Specifications for I/O module with 7 or 10 inputs/outputs
Supply voltage 24 V AC ± 15 %, 50 Hz
Power consumption 2.5 VA
Ambient temperature 0…50°C
Storage temperature -20…70°C
Ambient humidity Max. 90 % RH
Protection class IP20
Communication EXOline RS485
Communication speed 9600 bps
Built-in temperature sensor NTC type, measuring range 0...50°C
Accuracy ±0.5°C at 15...30°C
Material, casing Polycarbonate (PC)
Weight 110
Analogue inputs (AI) PT1000, 0...50°C
Condensation input (CI) Input for Regin's condensation detector KG-A/1
Digital inputs (DI) Closing potential-free contact
Universal inputs (UI) Analogue input (AI), PT1000 sensor, 0...100°C or digital input (DI)
Digital outputs (DO) 24 V AC, max. 0.5 A.
Universal outputs (UO) Digital output (DO) 24 V AC, max. 2.0 A or analogue output (AO), 0...10 V DC

Other documentation