SSCU100-60-HR-PO Flanged ultrasonic energy meters
Flanged ultrasonic energy meters, intended for heating or cooling.We offer many different options, see the product sheet for more information.
Specifications
Power Supply | Exchangeable 3 V lithium battery, estimated lifetime 10 years. 24 V or 230 V power pack available as accessory. |
---|---|
Nominal diameter | DN100 |
Flow, Qp | 60 m³/h |
Type of measurement | Heating |
Communication interface | Pulse output for energy |
Length of flow meter | 360 mm |
Media | Water only |
Protection class | IP54 |
---|---|
Ambient humidity (non-condensing) | 5…95 % RH |
Storage temperature | 1…60 °C |
Temperature range cooling | 0...50 °C |
Temperature range heating | 0...150 °C |
Temperature resolution | 0.01 °C |
Measurement cycle, temperature | 2...60 s |
Measurement cycle, flow | 2 s |
Display | LCD, 8 digits + special characters |
Display units | MWh, kW, GJ, m 3 , m 3 /h (kWh, GJ, l , l/h, MW, MMBTU, Gcal), 3 decimal places. The unit for energy consumption can only be set while the energy consumption is ≤ 10 kWh. |
Mechanical class | Class M2 (MID: 31.03.2004 annex I) |
EMC | Class E2 (MID: 31.03.2004 annex I) |
Cable length temperature sensor | 3 m |
Diameter temperature sensor | 6 mm |
Temperature sensor installation | Indirect in a temperature sensor pocket per EN1434 |
Temperature sensor requirements, heat meter | EU (MID) identification on the temperature sensors |
Temperature sensor requirements, cooling meter | National German approval as a temperature sensor for cooling meters. Requirements in other countries may be different |
Flow meter mounting position | Horizontal or vertical, the transducers (black housing) to the side of or under the measuring tube for cooling applications |
Flow meter, point of installation | Return flow (if forward flow installation is needed, the installation position can be changed with the main button) |
Flow meter temperature range | Heating 10…130 °C |
Measuring principle | Ultrasonic; time-of-flight |
Accuracy according to MID | Class 2 |
Software & documentation
Other documentation
Accessories



Regin
TH-85-1/2
Temperature sensor pocket for installation of universal temperature sensor with 6 mm sheath diameter
- Compatible with
- q p 3.5…10 m 3 /h
- Connection A
- G½
- Installation length
- 85 mm

Regin
TH-120-1/2
Temperature sensor pocket for installation of universal temperature sensor with 6 mm sheath diameter
- Compatible with
- 15...100 m³/h
- Connection A
- G1/2"
- Installation length
- 120 mm