Navigate on this page
Articles
(5 st)-
RDAS18S-23018 Nm, on/off, 230 V, spring return
- Supply voltage
- 230 V AC
- Power consumption
- 8 VA (6W - Running / 4 W - Holding)
- Cable length
- 0.9 m
- Torque
- 18 Nm
- Running time, actuator
- 90 s
- Running time, spring
- 15 s
- Auxiliary switch
- No
- Angle limitation
- 95 °
- Damper shaft, round
- 8…25.6 mm
- Damper shaft, square
- 6…18 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 3 m²
-
RDAS18S-230S18 Nm, on/off, 230 V, spring return, aux. switch
- Supply voltage
- 230 V AC
- Power consumption
- 8 VA (6W - Running / 4 W - Holding)
- Cable length
- 0.9 m
- Torque
- 18 Nm
- Running time, actuator
- 90 s
- Running time, spring
- 15 s
- Auxiliary switch
- Yes
- Angle limitation
- 95 °
- Damper shaft, round
- 8…25.6 mm
- Damper shaft, square
- 6…18 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 3 m²
-
RDAS18S-2418 Nm, on/off, 24 V, spring return
- Supply voltage
- 24 V AC/DC
- Power consumption
- 7 VA (5W - Running / 3W - Holding)
- Cable length
- 0.9 m
- Torque
- 18 Nm
- Running time, actuator
- 90 s
- Running time, spring
- 15 s
- Auxiliary switch
- No
- Angle limitation
- 95 °
- Damper shaft, round
- 8…25.6 mm
- Damper shaft, square
- 6…18 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 3 m²
-
RDAS18S-24S18 Nm, on/off, 24 V, spring return, aux. switch
- Supply voltage
- 24 V AC/DC
- Power consumption
- 7 VA (5W - Running / 3W - Holding)
- Cable length
- 0.9 m
- Torque
- 18 Nm
- Running time, actuator
- 90 s
- Running time, spring
- 15 s
- Auxiliary switch
- Yes
- Angle limitation
- 95 °
- Damper shaft, round
- 8…25.6 mm
- Damper shaft, square
- 6…18 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 3 m²
-
RDAS18S-24A18 Nm, 0-10 V, 24 V, spring return
- Supply voltage
- 24 V AC/DC
- Power consumption
- 7 VA (5W - Running / 3W - Holding)
- Cable length
- 0.9 m
- Torque
- 18 Nm
- Running time, actuator
- 90 s
- Running time, spring
- 15 s
- Auxiliary switch
- No
- Angle limitation
- 95 °
- Damper shaft, round
- 8…25.6 mm
- Damper shaft, square
- 6…18 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 3 m²
Specifications
Appliance class | Class III |
---|---|
Protection class | IP54 |
Ambient humidity (non-condensing) | 0…95 % RH |
Storage temperature | -32…70 °C |
Cable nominal cross section | 0.75 mm² |
Cable length extension, maximum | 300 m |
Working angle, rotation | 90 ° |