Regin

Temperature, humidity and CO2 transmitter for duct mounting

0…10 V duct transmitter for temperature, relative humidity and carbon dioxide measurements in air.

Articles

(3 st)
  • DTTHC - Regin
    DTTHC
    Temperature, humidity and CO2 transmitter
    Sensor Interface
    0-10 V
    Display
    No
    AO
    3
    Max air velocity
    20 m/s
    Media temp limits
    -40…60 °C
    Insertion length
    37…195 mm
    Max Overvoltage on any terminal
    +10 V (refereras till GND) V
    Analogue output load impedance 0...10v
    Min. 10 kΩ
    Measuring range, temp
    -40…60 °C
    Sensor element protection, humidity
    Membrane filter, not exchangeable
    Accuracy, humidity 1
    ±2 % RH @ 10...90 % RH
    Accuracy, humidity 2
    ±3 % RH @ 0...10 & 90...100 % RH
    Accuracy, gas in air
    ±(50 ppm + 3 % of the measured value) @ 25 °C
    Warm-up time
    4min
    Temperature dependance
    2.5 ppm/K at 0…50 °C
  • DTTH - Regin
    DTTH
    Temperature and humidity transmitter
    Sensor Interface
    0-10 V
    Display
    No
    AO
    2
    Max air velocity
    20 m/s
    Media temp limits
    -40…60 °C
    Insertion length
    37…195 mm
    Max Overvoltage on any terminal
    +10 V (refereras till GND) V
    Analogue output load impedance 0...10v
    Min. 10 kΩ
    Measuring range, temp
    -40…60 °C
    Sensor element protection, humidity
    Membrane filter, not exchangeable
    Accuracy, humidity 1
    ±2 % RH @ 10...90 % RH
    Accuracy, humidity 2
    ±3 % RH @ 0...10 & 90...100 % RH
    Accuracy, gas in air
    ±(50 ppm + 3 % of the measured value) @ 25 °C
    Warm-up time
    4min
    Temperature dependance
    2.5 ppm/K at 0…50 °C
  • DTTC - Regin
    DTTC
    Sensor Interface
    0-10 V
    Display
    No
    AO
    2
    Max air velocity
    20 m/s
    Media temp limits
    -40…60 °C
    Insertion length
    37…195 mm
    Max Overvoltage on any terminal
    +10 V (refereras till GND) V
    Analogue output load impedance 0...10v
    Min. 10 kΩ
    Measuring range, temp
    -40…60 °C
    Accuracy, gas in air
    ±(50 ppm + 3 % of measured value) @ 25 °C
    Warm-up time
    4min
    Temperature dependance
    2.5 ppm/K at 0…50 °C

Specifications

Specifications for Temperature, humidity and CO2 transmitter for duct mounting
Power Supply 24VAC/DC (20...28 V AC 50/60Hz / 15...35 V DC), 2.0 VA
Protection class IP65
Ambient humidity (non-condensing) 0…90 % RH
Ambient temperature -40…60 °C
Storage temperature -40…80 °C
Storage humidity 0...90 % RH
Dimensions, external (WxHxD) 104x212x79 mm
Weight, incl. packaging 0.25 kg
Accuracy, temperature 0,2 K
Accuracy, temperature 1 ±0.2 °K @ 0...60 °C
Accuracy, temperature 2 ±0.8 °K @ -40...0 & >60 °C
Measuring range, humidity 0…100 % RH
Measuring range, gas in air 0…2000 ppm
Response time <100s, <50s
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
Material, housing Polykarbonat (PC)
Material, cover Polykarbonat (PC)
Material, base ABS

Accessories

HA010103
Regin HA010103

Sintered stainless steel filter, protection in demanding environments

HA010105
Regin HA010105

Teflon filter

HA010106
Regin HA010106

Metal filter

HA010102
Regin HA010102

Sintered brass filter, protection in demanding environments

You´re on France site
Change language? English français (France)
Change sales company?
Benelux Denmark Germany (Redirect to: deos-ag.com) International Italy (Redirect to: industrietechnik.it) Sweden