Regin

DTTC Temperature and CO 2 transmitter for duct mounting

0…10 V duct transmitter for temperature and carbon dioxide measurements in air.

Specificaties

Specificaties voor DTTC
Dimensions, external (WxHxD) 104*212*79 mm
AO 2
Max air velocity 20 m/s
Media temp limits -40…60 °C
Insertion length 37…195 mm
Max Overvoltage on any terminal +10 V (refereras till GND) V
Analogue output load impedance 0...10v Min. 10 kΩ
Measuring range, temp -40…60 °C
Output temperature 0-10 V
Measuring range, gas in air 0…2000 ppm
Output signal, gas in air 0-10 V
Accuracy, gas in air ±(50 ppm + 3 % of measured value) @ 25 °C
Response time <100s
Warm-up time 4min
Temperature dependance 2.5 ppm/K at 0…50 °C
Specificaties voor Temperature and CO2 transmitter for duct mounting
Power Supply 24VAC/DC (20...28 V AC 50/60Hz / 15...35 V DC), 2.0 VA
Protection class IP65
Ambient humidity (non-condensing) 0…90 % RH
Ambient temp -40…60 °C
Storage temp -40…80 °C
Storage humidity 0...90 % RH
Weight, incl. packaging 0.25 kg
Accuracy, temperature ± 0,2 K
Accuracy, temperature 1 ±0.2 °K @ 0...60 °C
Accuracy, temperature 2 ±0.8 °K @ -40...0 & >60 °C
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
Material, housing Polykarbonat (PC)
Material, cover Polykarbonat (PC)
Material, base ABS