Regin

SSU25-6.0-CR-PO Compact ultrasonic energy meters

Externally threaded, compact energy meters with built-in ultrasonic flow meter, intended for heating or cooling. We offer many different options, see the product sheet for more information.

Specifications

Specifications for SSU25-6.0-CR-PO
Nominal diameter DN25
Flow, Qp 6 m³/h
Type of measurement Cooling
Communication interface Pulse output for energy
Length of flow meter 150 mm
Thread on meter body G1 1/4"
Media Water only
Specifications for Compact ultrasonic energy meters
Power Supply Exchangeable 3 V lithium battery, estimated lifetime 10 years. 24 V or 230 V power pack available as accessory.
Protection class IP65
Ambient humidity (non-condensing) 5…95 % RH
Ambient temp 5…55 °C
Storage temp 1…60 °C
Temperature range cooling 0...50 °C
Temperature range heating 15...90 °C
Temperature resolution 0.01 °C
Measurement cycle, temperature 2...60 s
Measurement cycle, flow 2 s
Interfaces M-Bus, pulse output or M-Bus with 3 pulse inputs
Display LCD, 8 digits + special characters
Display units MWh, kW, GJ, m 3 , m 3 /h (kWh, GJ, l , l/h, MW, MMBTU, Gcal), 3 decimal places. The unit for energy consumption can only be set while the energy consumption is ≤ 10 kWh.
Mechanical class Class M1 (MID: 31.03.2004 annex I)
EMC Class E1 (MID: 31.03.2004 annex I)
Cable length calculator 85 cm
Cable length temperature sensor 1.5 m (the other temperature sensor is integrated into the flow meter)
Diameter temperature sensor 5 mm
Temperature sensor installation Direct (see the accessories section) or indirect in a temperature sensor pocket per EN1434
Temperature sensor requirements, heat meter EU (MID) identification on the temperature sensors
Temperature sensor requirements, cooling meter National German approval as a temperature sensor for cooling meters. Requirements in other countries may be different
Flow meter mounting position Horizontal or vertical
Flow meter, point of installation Return flow (if forward flow installation is needed, the installation position can be changed with the main button)
Flow meter temperature range 15…90 °C
Measuring principle Ultrasonic, time-of-flight
Accuracy according to MID Class 2