DTTH Temperature, humidity and CO 2 transmitter for duct mounting

Temperature and humidity transmitter

Specifications

Specifications for DTTH
Sensor Interface 0-10 V
Display No
AO 2
Max air velocity 20 m/s
Media temp limits -40…60 °C
Insertion length 37…195 mm
Max Overvoltage on any terminal +10 V (refereras till GND) V
Analogue output load impedance 0...10v Min. 10 kΩ
Measuring range, temp -40…60 °C
Sensor element protection, humidity Membrane filter, not exchangeable
Accuracy, humidity 1 ±2 % RH @ 10...90 % RH
Accuracy, humidity 2 ±3 % RH @ 0...10 & 90...100 % RH
Accuracy, gas in air ±(50 ppm + 3 % of the measured value) @ 25 °C
Warm-up time 4min
Temperature dependance 2.5 ppm/K at 0…50 °C
Specifications for Temperature, humidity and CO2 transmitter for duct mounting
Power Supply 24VAC/DC (20...28 V AC 50/60Hz / 15...35 V DC), 2.0 VA
Protection class IP65
Ambient humidity (non-condensing) 0…90 % RH
Ambient temperature -40…60 °C
Storage temperature -40…80 °C
Storage humidity 0...90 % RH
Dimensions, external (WxHxD) 104x212x79 mm
Weight, incl. packaging 0.25 kg
Accuracy, temperature 0,2 K
Accuracy, temperature 1 ±0.2 °K @ 0...60 °C
Accuracy, temperature 2 ±0.8 °K @ -40...0 & >60 °C
Measuring range, humidity 0…100 % RH
Response time <50s
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
Material, housing Polykarbonat (PC)
Material, cover Polykarbonat (PC)
Material, base ABS

Accessories

HA010103
Regin HA010103

Sintered stainless steel filter, protection in demanding environments

HA010105
Regin HA010105

Teflon filter

HA010106
Regin HA010106

Metal filter

HA010102
Regin HA010102

Sintered brass filter, protection in demanding environments