Corrigo Ardo 3.6, E models - configurable controllers for ventilation.
Corrigo comes preloaded with applications for control of ventilation.
Corrigo running a ventilation application is intended for control of air handling units with temperature control, 1- or 2-speed operation or, alternatively, pressure or air flow control of supply air fan and extract air fan, humidity control as well as other common functions in ventilation.
Navigate on this page
Articles
(1 st)-
E283DW-3
- Dimensions, external (WxHxD)
- 149*121*60 mm
- Number of modules
- 8.5
- Display
- Yes
- Display type
- Backlit (LCD), 4 rows of 20 characters
- Supported protocols
- EXOline, Modbus, BACnet
- RS485 ports
- 2
- Ethernet ports
- 1
- Display ports
- 1
- AI
- 4
- UI
- 4
- DI
- 8
- CI
- 0
- AO
- 5
- UO
- 0
- DO
- 7
Specifications
Power Supply | 24VAC/DC (21...27 V AC 50/60Hz / 20...36 V DC), 12.0 VA |
---|---|
Battery type | CR2032 replacable Lithium cell |
Battery life time | 5 years |
Protection class | IP20 |
Ambient humidity (non-condensing) | 0…90 % RH |
Ambient temp | 0…50 °C |
Storage temp | -20…70 °C |
Mounting | Cabinet, DIN-rail |
Analogue inputs type (AI) | PT1000/Ni1000/Ni1000LG/0-10 V |
Terminal type | Screw Terminal |
Detachable terminal | Yes |
Terminal wire size | 3 mm² |
Material, housing | Polycarbonate (PC) |
Material, base | Polycarbonate (PC) |
The Corrigo* controllers are BTL listed
Software & documentation
Software
Product sheet
Instructions
Manuals
- Corrigo ventilation 3.6 (EN)
- Corrigo ventilation 3.X user guide (EN)
- Corrigo ventilation 3.X user guide (TR)
- Corrigo ventilation 3.X user guide (DA)
- Corrigo ventilation 3.X user guide (LV)
- Corrigo ventilation 3.X user guide (SK)
- Corrigo ventilation 3.X user guide (ES)
- Corrigo ventilation 3.X user guide (SI)
- Corrigo ventilation 3.X user guide (HU)
- Corrigo ventilation 3.X user guide (RU)
- Corrigo ventilation 3.X user guide (RO)
- Corrigo ventilation 3.X user guide (CZ)
- Corrigo ventilation 3.X user guide (PT)
- Corrigo ventilation 3.X user guide (PL)
- Corrigo ventilation 3.X user guide (NO)
- Corrigo ventilation 3.X user guide (LT)
- Corrigo ventilation 3.X user guide (NL)
- Corrigo ventilation 3.X user guide (FI)
- Corrigo ventilation 3.X user guide (ET)
Other documentation
- Corrigo ventilation variables for EXOline Modbus and BACnet 3.6 (EN)
- CAB-STD2-3 Corrigo ventilation 3.6 editable (EN)
- CAB-STD1-3 Corrigo ventilation 3.4 editable (EN)
- Information on updates in Corrigo ventilation (from version 3.3-1-25) (EN)
- Env. decl. (EN)
- Corrigo ventilation 3.6 BACnet Object Types
- Corrigo ventilation 3.6 BACnet EDE
Accessories
External display
3 m cable for connecting an external display
Cable for USB connection
10 m cable for connecting an external display
Set of plug-in terminals for models with 15 I/O:s
Set of plug-in terminals for models with 28 I/O:s
Ardo expansion unit with15 I/O:s
Ardo expansion unit with 28 I/O:s
Vido expansion unit with 19 I/O:s
Front mounting kit, room for one controller
Configuration tool ventilation 3.6
External graphic touch display