ZTV / ZTR - 2- and 3-way control valves DN15-25, kvs 0.25-7.0, 5.5 mm stroke
Valves used for control of hot and cold water in climate, heating and ventilation systems. They can also control glycol-mixed water in for example liquid connected recovery systems. Intended to be used together with the RVAZ4 actuators.
Navigate on this page
Articles
(20 st)-
ZTV15-0,25
- Nominal diameter
- DN15
- Kvs
- 0.25 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTV15-0,4
- Nominal diameter
- DN15
- Kvs
- 0.4 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTV15-0,6
- Nominal diameter
- DN15
- Kvs
- 0.6 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTV15-1,0
- Nominal diameter
- DN15
- Kvs
- 1.0 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTV15-1,6
- Nominal diameter
- DN15
- Kvs
- 1.6 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTV20-2,0
- Nominal diameter
- DN20
- Kvs
- 2.0 m3/h
- Connection
- G3/4"
- Max. diff. pressure
- 250 kPa
- Actuator
- RVAZ4
-
ZTV20-2,5
- Nominal diameter
- DN20
- Kvs
- 2.5 m3/h
- Connection
- G3/4"
- Max. diff. pressure
- 250 kPa
- Actuator
- RVAZ4
-
ZTV20-4,0
- Nominal diameter
- DN20
- Kvs
- 4.0 m3/h
- Connection
- G3/4"
- Max. diff. pressure
- 150 kPa
- Actuator
- RVAZ4
-
ZTV20-6,0
- Nominal diameter
- DN20
- Kvs
- 6.0 m3/h
- Connection
- G3/4"
- Max. diff. pressure
- 150 kPa
- Actuator
- RVAZ4
-
ZTV25-7,0
- Nominal diameter
- DN25
- Kvs
- 7.0 m3/h
- Connection
- G1"
- Max. diff. pressure
- 70 kPa
- Actuator
- RVAZ4
-
ZTR15-0,25
- Nominal diameter
- DN15
- Kvs
- 0.25 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTR15-0,4
- Nominal diameter
- DN15
- Kvs
- 0.4 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTR15-0,6
- Nominal diameter
- DN15
- Kvs
- 0.6 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTR15-1,0
- Nominal diameter
- DN15
- Kvs
- 1.0 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTR15-1,6
- Nominal diameter
- DN15
- Kvs
- 1.6 m3/h
- Connection
- G1/2"
- Max. diff. pressure
- 350 kPa
- Actuator
- RVAZ4
-
ZTR20-2,0
- Nominal diameter
- DN20
- Kvs
- 2.0 m3/h
- Connection
- G3/4"
- Max. diff. pressure
- 250 kPa
- Actuator
- RVAZ4
-
ZTR20-2,5
- Nominal diameter
- DN20
- Kvs
- 2.5 m3/h
- Connection
- G3/4"
- Max. diff. pressure
- 250 kPa
- Actuator
- RVAZ4
-
ZTR20-4,0
- Nominal diameter
- DN20
- Kvs
- 4.0 m3/h
- Connection
- G3/4"
- Max. diff. pressure
- 100 kPa
- Actuator
- RVAZ4
-
ZTR20-6,0
- Nominal diameter
- DN20
- Kvs
- 6.0 m3/h
- Connection
- G3/4"
- Max. diff. pressure
- 100 kPa
- Actuator
- RVAZ4
-
ZTR25-7,0
- Nominal diameter
- DN25
- Kvs
- 7.0 m3/h
- Connection
- G1"
- Max. diff. pressure
- 70 kPa
- Actuator
- RVAZ4
Specifications
Application | Heating systems, cooling systems, fan-coil units, ventilation systems |
---|---|
Pressure rating | PN16 |
Connection, actuator | M30 x 1.5 |
Connection | BSP externally threaded according to ISO 228/1 |
Flow characteristics | Equal percentage |
Max. leakage | 0 % of the kvs value |
Media | Hot water, cold water, glycol-mixed water |
Media temperature | 1…110°C |
Rangeability | 50:1 |
Stroke | 5.5mm |
Body | Brass CW614N |
Seat | Brass CW614N |
Plug | Brass CW614N |
Stem | Stainless steel 1.4305 |
Seat packing | EPDM |
O-rings | EPDM |