CO2, temperature and humidity transmitter, room mounting

Transmitters for wall mounting with or without display.

Articles

(4 st)
  • CTHR - Regin
    CTHR
    CO2 + RH + PT1000, 1000 Ohm (0°C)
    Accuracy, temperature
    ± 0.3 °C
    Output, CO 2
    0…10 V DC
    Output, humidity
    0…10 V DC
    Output, temperature
    PT1000
    Display
    -
  • CTHR-D - Regin
    CTHR-D
    CO2 + °C + RH
    Accuracy, temperature
    ± 0.3 °C
    Output, CO 2
    0…10 V DC
    Output, humidity
    0…10 V DC
    Output, temperature
    PT1000
    Display
    X
  • CTHRA - Regin
    CTHRA
    CO2 + °C + RH
    Accuracy, temperature
    ± 0.4 °C
    Output, CO 2
    0…10 V DC
    Output, humidity
    0…10 V DC
    Output, temperature
    0…10 V DC
    Display
    -
  • CTHRA-D - Regin
    CTHRA-D
    CO2 + °C + RH
    Accuracy, temperature
    ± 0.4 °C
    Output, CO 2
    0…10 V DC
    Output, humidity
    0…10 V DC
    Output, temperature
    0…10 V DC
    Display
    X
Specifications for CO 2 , temperature and humidity transmitter, room mounting
Supply voltage 24 V AC/DC (22…26 V AC / 15…35 V DC)
Working range, CO 2 0…2000ppm
Accuracy, CO 2 < ± (50 ppm + 2 % of the measured value)
Working range, temperature 0…50°C
Accuracy, temperature ±0.3°C
Working range, humidity 10…90% RH
Accuracy, humidity ±3 %
Power consumption < 2.5 W
Energy consumption < 0.5 Wh
Transformer power ≥ 5 VA
Mounting Room
Dimensions 100 x 85 x 30.5mm
Protection class IP30

Other documentation