CTRTA CO 2 and temperature transmitter, room mounting

CO2 and temperature transmitter

Specificaties

Specificaties voor CTRTA
Accuracy, temperature ± 0.4 °C (0…10 V), ± 0.3 °C (PT1000)
Output, temperature 0…10 V DC + PT1000
Output, CO 2 0…10 V DC
Display [False]
Specificaties voor CO2 and temperature transmitter, room mounting
Supply voltage 24 V AC/DC (22…26 V AC / 15…35 V DC)
Working range, CO 2 0…2000ppm
Accuracy, CO 2 < ± (50 ppm + 2 % of the measured value)
Working range, temperature 0…50°C
Power consumption < 2.5 W
Energy consumption < 0.5 Wh
Transformer power ≥ 5 VA
Mounting Room
Dimensions 100 x 85 x 30.5mm
Protection class IP30