Electric heating controller for external signal 0-10 V, 230/400 V AC, DIN-rail mounting

Electric heating controllers intended for control of radiators or electric heating coils. They can be mounted on a DIN-rail in a cabinet. The electric heating controllers utilise time-proportional triac control and operate on an external 0...10 V input signal.

Artikelen

(1 st)
  • PULSER-X/D - Regin
    PULSER-X/D
    Electric heating controller for external 0...10 V DC control signal

Specificaties

Specificaties voor Electric heating controller for external signal 0-10 V, 230/400 V AC, DIN-rail mounting
Supply voltage 230 V ~ (207...253 V ~ 50/60 Hz 16 A) or 400 V ~ (360...440 V ~ 50/60 Hz), automatic adaption to supplied voltage
Pulse period 6/60/120 s, adjustable
Mounting DIN-rail
Power dissipation 20 W of heat at full load
Protection class IP20
Ambient temperature 0…40°C
Ambient humidity Max. 90 % RH, non-condensing
Storage temperature -40…+50°C
Number of modules 6.6
Cable connection Cage clamp
Input signal 0...10 V DC
Output load Resistive load, max 16 A, min 1 A
Dimensions (WxHxD) 115 x 88 x 59mm
Weight (incl. packaging) 0.42 kg