Specificaties
Pressure rating | PN16 |
---|---|
Connection | Flanges according to ISO 7005-2 |
Flow characteristics | Equal percentage |
Max. diff. pressure | 1600kPa |
Max. leakage | 0.0 % of kvs (PTFE packing with 25 % carbon, no leakage) |
Media temperature | -5...+140°C |
Media | Hot, cold, glycol-mixed water or steam |
Rangeability | 100:1 |
Stroke | 20mm |
Material | |
Body | Bronze SS5204 |
Plug and seat | Stainless steel |
Stem | Stainless steel |
O-rings | Viton |
Accessoires

S6321457301