Regin
RDAS 10 Nm
Damper actuator without spring return, 10 Nm. For 2-point (on/off)/3-point or 0…10 V control signal.
Articles
(5 st)-
RDAS10-23010 Nm, on/off or 3-point, 230 V- Supply voltage
- 230 V AC
- Power consumption
- 6 VA (2 W - Running / 0.9 W - Holding)
- Cable length
- 0.9 m
- Torque
- 10 Nm
- Control signal
- 2-point (on/off)/3-point
- Running time, actuator
- 150 s
- Auxiliary switch
- No
- Angle limitation
- 95 °
- Damper shaft, round
- 8…16 mm
- Damper shaft, square
- 6…12.8 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 1.6 m²
-
RDAS10-230S10 Nm, on/off or 3-point, 230 V, aux.switch- Supply voltage
- 230 V AC
- Power consumption
- 6 VA (2 W - Running / 0.9 W - Holding)
- Cable length
- 0.9 m
- Torque
- 10 Nm
- Control signal
- 2-point (on/off)/3-point
- Running time, actuator
- 150 s
- Auxiliary switch
- Yes
- Angle limitation
- 95 °
- Damper shaft, round
- 8…16 mm
- Damper shaft, square
- 6…12.8 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 1.6 m²
-
RDAS10-2410 Nm, on/off or 3-point, 24 V- Supply voltage
- 24 V AC/DC
- Power consumption
- 2.2 VA (1.3 W - Running / 0.5 W - Holding)
- Cable length
- 0.9 m
- Torque
- 10 Nm
- Control signal
- 2-point (on/off)/3-point
- Running time, actuator
- 150 s
- Auxiliary switch
- No
- Angle limitation
- 95 °
- Damper shaft, round
- 8…16 mm
- Damper shaft, square
- 6…12.8 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 1.6 m²
-
RDAS10-24S10 Nm, on/off or 3-point, 24 V, aux. switch- Supply voltage
- 24 V AC/DC
- Power consumption
- 2.2 VA (1.3 W - Running / 0.5 W - Holding)
- Cable length
- 0.9 m
- Torque
- 10 Nm
- Control signal
- 2-point (on/off)/3-point
- Running time, actuator
- 150 s
- Auxiliary switch
- Yes
- Angle limitation
- 95 °
- Damper shaft, round
- 8…16 mm
- Damper shaft, square
- 6…12.8 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 1.6 m²
-
RDAS10-24A10 Nm, 0-10 V, 24 V- Supply voltage
- 24 V AC/DC
- Power consumption
- 2.2 VA (1.3 W - Running / 0.5 W - Holding)
- Cable length
- 0.9 m
- Torque
- 10 Nm
- Control signal
- 0(2)…10 V DC
- Feedback signal
- 0...10 V DC
- Running time, actuator
- 150 s
- Auxiliary switch
- No
- Angle limitation
- 95 °
- Damper shaft, round
- 8…16 mm
- Damper shaft, square
- 6…12.8 mm
- Damper shaft, min shaft length
- 20 mm
- Max damper size (area)
- 1.6 m²
Specifications
| Appliance class | Class III |
|---|---|
| Protection class | IP54 |
| Ambient humidity (non-condensing) | 0…95 % RH |
| Storage temperature | -32…70 °C |
| Cable nominal cross section | 0.75 mm² |
| Cable length extension, maximum | 300 m |
| Working angle, rotation | 90 ° |
Software & documentation
Product sheets
Instructions
Product declarations