RTV - 2-way radiator/zone valve, DN10-15, fixed kvs

Range of zone valves for control in aftertreatment systems. The valve can control water flow to cooling and heating batteries, radiators, convectors, chilled ceilings etc. and is intended to be used with the RTA(O)M100 thermal actuators.

Articles

(2 st)
  • RTV10
    RTV10
    Nominal diameter
    DN10
    Connection, internal thread
    G3/8”
    Connection, external thread
    M22 x 1.5
    Kvs
    1.2 m3/h
    ΔPmax
    30 kPa
    ΔPs
    150 kPa
    Actuator
    RTA(O)M
  • RTV15
    RTV15
    Nominal diameter
    DN15
    Connection, internal thread
    G1/2”
    Connection, external thread
    M26 x 1.5
    Kvs
    1.4 m3/h
    ΔPmax
    30 kPa
    ΔPs
    150 kPa
    Actuator
    RTA(O)M
Specifications for RTV - 2-way radiator/zone valve, DN10-15, fixed kvs
Application Heating systems, cooling systems, radiators, radiant cooling, ventilation systems
Pressure rating PN10
Connection, actuator M28 x 1.5
Max. leakage 0 % of the kvs value
Max. diff. pressure 250kPa
Media Hot water, cold water, glycol-mixed water
Media temperature 5…100°C
Stroke 1.7mm
Body Chromed brass CW614N
Seat Brass CW614N
Stem Stainless steel 1.4305
O-rings EPDM
Bonnet Brass CW614N
Seat packing NBR
4161201

Tail and nut, for valve outlet (external metric thread on the valve)

4161202

Tail and nut, for valve outlet (external metric thread on the valve)

4161841

Nut and olive, for valve outlet (external metric thread on the valve)

4160801

Nut and olive, for valve outlet (external metric thread on the valve)

4161402

Nut and olive, for valve inlet (internal pipe thread on the valve)

4161403

Nut and olive, for valve inlet (internal pipe thread on the valve)

4161101

Nut and olive, for valve inlet (internal pipe thread on the valve)

4161102

Nut and olive, for valve inlet (internal pipe thread on the valve)

4161103

Nut and olive, for valve inlet (internal pipe thread on the valve)