Thermal actuators 125 N, 6.5 mm stroke

Thermal actuators with position indication for control of valves in heating or cooling systems. The actuator can be used to control radiator circuits, solar heating systems, heating or cooling coils, floor heating, etc.

Articles

(5 st)
  • RTAM125-24
    RTAM125-24
    Thermal actuator
    Supply voltage
    24 V AC/DC
    Control signal
    On/off, NC
    Power consumption
    1.2 W. Max. inrush current < 300 mA during max. 2 min.
    Stroke time
    4.5 min
    Force
    125 N
    Stroke
    6.5 mm
  • RTAOM125-24
    RTAOM125-24
    Thermal actuator
    Supply voltage
    24 V AC/DC
    Control signal
    On/off, NO
    Power consumption
    1.2 W. Max. inrush current < 300 mA during max. 2 min.
    Stroke time
    4.5 min
    Force
    125 N
    Stroke
    6.5 mm
  • RTAM125-24A
    RTAM125-24A
    Thermal actuator
    Supply voltage
    24 V AC
    Control signal
    0...10 V DC, NC
    Power consumption
    1.2 W. Max. inrush current < 300 mA during max. 2 min.
    Stroke time
    30 s/mm
    Force
    125 N
    Stroke
    6.5 mm
  • RTAM125-230
    RTAM125-230
    Thermal actuator
    Supply voltage
    230 V AC
    Control signal
    On/off, NC
    Power consumption
    1.2 W. Max. inrush current < 550 mA during max. 100 ms.
    Stroke time
    4.5 min
    Force
    125 N
    Stroke
    6.5 mm
  • RTAOM125-230
    RTAOM125-230
    Thermal actuator
    Supply voltage
    230 V AC
    Control signal
    On/off, NO
    Power consumption
    1.2 W. Max. inrush current < 550 mA during max. 100 ms.
    Stroke time
    4.5 min
    Force
    125 N
    Stroke
    6.5 mm
Specifications for Thermal actuators 125 N, 6.5 mm stroke
Ambient temperature 0…60°C
Storage temperature -25…+65°C
Protection class IP54
Installation Snap-on
Cable length 2m
Weight 100 g (24 V AC/DC, 230 V AC), 111 g (24 V AC)
RTA-CASE

Adapter case containing an assortment of adapters for testing on site

VA54

Adapter, M28 x 1.5 mm