Additional I/O units
Additional I/O unit for EXOcompact and EXOclever with 16 supplementary I/Os per Add:io. Possibility to expand an EXOclever controller with unlimited I/Os and an EXOcompact with up to 50 I/Os. The Add:io units fit smoothly together, requiring minimal space.
Navigate on this page
Articles
(2 st)-
IO-EC16UID-X
- Universal input d (UId)
- 16
- Universal output b (UOb)
- -
-
IO-EC16UOB-X
- Universal input d (UId)
- -
- Universal output b (UOb)
- 16
Specifications
Supply voltage | 24 V AC/DC (18…26 V AC / 22…30 V DC) |
---|---|
Power consumption, nominal | IO-…16UOb: 7.8 VA / 3.5 W IO-…16UIc and …16UId: 4.5 VA / 1.8 W |
Protection class | IP20 |
Ambient humidity | Max. 95 % RH |
Ambient temperature | 0…55°C |
Ambient temperature, electronics | 0…55°C |
Storage temperature | -20…+70°C |
Mounting | DIN-rail |
Number of modules | 8 |
Inputs/outputs (I/Os) | 16 per Add:io |
Display | No |
Indication type | LED for communication info |
Dimensions, external (WxHxD) | 140 x 136 x 46 mm |
Weight (incl. packaging) | 0.30 kg |
Port type | RS485 |
Default protocol | EFX |
Supported protocols | EFX slave |
Port isolation | Yes |
Communication speed | 115200 bps |
Cable connection | Push-in connectors |
Universal input c (UIc) | AI: 0…10 V, 800…1600 Ω (Pt1000, Ni1000 LG, Ni1000 DIN), 0…4000 Ω (Pt1000 ext, Ni1000 LG ext, Ni1000 DIN ext) DI: Sourcing input type, GND is ref |
Universal input d (UId) | AI: 0…10 V, 0(4)…20 mA, 800…1600 Ω (Pt1000, Ni1000 LG, Ni1000 DIN), 0…4000 Ω (Pt1000 ext, Ni1000 LG ext, Ni1000 DIN ext) DI: Sourcing input type, GND is ref |
Universal output b (UOb) | AO: 0…10 V DC, short-circuit protected DO: 24 V AC/DC sinking MOSFET, DC short-circuit protected |
Material, housing | Polycarbonate, PC |