DTV1000X Differential pressure switch for air and non-corrosive gases

Differential pressure switch for supervising air handling units, fans, filters or to control defrosting functions.

Specifications

Specifications for DTV1000X
Relay NO/NC
Max. switching load 1.5A
Min. switching load 0,4A
Switch capacity Over 1000 000 switching operations
Pressure, range sensor 200…1000 Pa
Max. allowed diff. Pressure sensor 1 10 kPa
Hysteresis 100 Pa ± 15 %
Specifications for Differential pressure switch for air and non-corrosive gases
Protection class IP54
Ambient temp -20…85 °C
Storage temp -40…85 °C
Weight, incl. packaging 0.17 kg
Media Air and non-corrosive gases
Material, housing Polystyrene
Material sensor Silicone membrane