HTDT10-420 Humidity/temperature transmitter ±2 % RH, for harsh environments

Humidity and temperature transmitter
Specifications for HTDT10-420
Supply voltage 20...30 V DC
Output signal 4...20 mA
Specifications for Humidity/temperature transmitter ±2 % RH, for harsh environments
Working range Humidity: 0...100 % RH. Temperature: -40...+60°C.
Accuracy, humidity ±2 % RH (0…90 % RH), ±3 % RH (90…100 % RH)
Accuracy, temperature ±0.2 K at 20°C
Insertion length 60…230mm
Mounting Duct
Protection class IP65
CCERT-E

Calibration certificate, when certified calibration is demanded. Must be ordered together with a new transmitter.