Exigo 3.4 – Controllers for heating and boiler control, 230 V

Exigo are controllers for heating and boiler control that make every step from installation to operation and maintenance easier than ever. Simply connect the controller, enter any settings as desired and start up. Exigo can be used either stand-alone or integrated into a network. It has built-in support for many different languages. Exigo is designed for mounting on a DIN-rail or in a cabinet door or over a device box. It can also be mounted directly on a wall. Exigo supports control of up to 3 heating circuits, 2 DHW circuits and boiler control of 1-4 boilers. It also has Delta T control over the heat exchanger.

The Exigo HC* controllers are BTL listed, click here to go to the BACnet International website where you'll find PICS documents and more information.

Articles

(4 st)
  • HC190D-1
    HC190D-1
    Communication ports
    -
    Inputs
    10
    Outputs
    9
    RS485 ports
    -
    TCP/IP ports
    -
    M-Bus ports
    -
    Display
    X
    Power consumption
    7.5 VA
  • HC191D-1
    HC191D-1
    Communication ports
    1
    Inputs
    10
    Outputs
    9
    RS485 ports
    1
    TCP/IP ports
    -
    M-Bus ports
    -
    Display
    X
    Power consumption
    7.5 VA
  • HC192DW-1
    HC192DW-1
    Communication ports
    2
    Inputs
    10
    Outputs
    9
    RS485 ports
    1
    TCP/IP ports
    1
    M-Bus ports
    -
    Display
    X
    Power consumption
    10 VA
  • HC193DWM-1
    HC193DWM-1
    Communication ports
    3
    Inputs
    10
    Outputs
    9
    RS485 ports
    1
    TCP/IP ports
    1
    M-Bus ports
    1
    Display
    X
    Power consumption
    10.5 VA
Specifications for Exigo 3.4 – Controllers for heating and boiler control, 230 V
Supply voltage 230 V AC
Ambient temperature 0...50°C
Storage temperature -20...+70°C
Ambient humidity Max. 95 % RH, non-condensing
Protection class IP20
Battery backup Memory and real-time clock function
Display 4 rows of 20 characters each, backlit
Analogue inputs (AI) PT1000 (-50…+150°C), Ni1000, 0…10 V
Digital inputs (DI) Potential-free closure
Universal analogue I/O (UA) Configurable 0…10 V DC; 2…10 V DC; 10…0 V DC or 10…2 V DC output (12 bit short-circuit protected) or 0…10 V DC input
Digital outputs (DO) 7x relay, 230 V AC, 1 A inductive load per relay
TCP/IP EXOline TCP, Modbus TCP, BACnet/IP, CLOUDigo
RS485 EXOline, Modbus, BACnet MS/TP
E3-DSP

External display

E0R-3

Repeater

E0R230K-3

Repeater

IO-A15MIXW-3-BEM

Ardo expansion unit with15 I/O:s

IO-A28MIXW-3-BEM

Ardo expansion unit with 28 I/O:s

IO-V19MIXW-1-BEM

Vido expansion unit with 19 I/O:s

E-CABLE-RS232

Cable for RS232 connection

E-CABLE2-USB

Cable for USB connection

E-CABLE-TCP/IP

Cable for TCP/IP connection directly to a PC

E-TOOL-HEATING-3.4-1-13

Configuration tool heating 3.4